8-Channel Analog Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
65
6.8
Module Restrictions
Restrictions for 8-Channel Analog Output MTA
(6ES7650-1AB51-2XX0 or 6ES7650-1AB50-2XX0)
I/O Module Restrictions
MTA Design
There is no Channel to Channel Isolation
MTA Design
Series diodes lower the output compliance
load to less than 600
Ω
MTA Design
Short Circuit to M not detected
MTA Design
SAO must be configured for Current Mode
MTA Design
Output Range: only 4-20mA & 0-20mA
Module Accuracy
Current Output
See Module Specs
6.9
Typical Load Connection to Field Terminals
Figure 6–2 Connecting an Analog Output to Field Terminals
SH 0
CH3-
CH1-
4 - 20 mA
LOAD
CH3+
+
CH1+
SH 1
SH 2
TB1
1
2
3
8
4
5
6
7
9
10
11
12
CH0+
CH2-
CH0-
SH 3
CH2+
-
1
Minimum 0, 22 mA cutoff current