8-Channel HART Analog Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
269
21.10 Hardware Configuration
The HART Analog Output MTA has no jumpers that affect the Module Hardware
Configuration.
Note
Redundant Operation. If a redundant HART Analog Output Module loses power
(module fuse opens) or is removed from service, then the output current will drop
to 50% of its value for several controller cycles.
21.10.1 Addresses
Non-redundant Operation
The choice of the Input Address and Process Image are left to the user.
Redundant Operation
Process Image should be set to something other than the default. The choice of
the Input Address is left to the user.
21.10.2 Outputs
For normal operation set
Type of Output
to current (
I
). The +/- 20 mA output range
is not possible due to the MTA Design. All other Module hardware configuration
choices under the
Outputs
tab are left to the user.
21.10.3 Redundancy
For non-redundant operation the value of the
Redundancy
field should be
None
.
21.11 Technical Specifications for 8-Channel HART Analog
Output Module (6ES7 332-8TF01-0AB0)
Note
For a complete functional description and the most current technical specifications
for this module, refer to the manual
ET 200M distributed I/O device HART analog
modules
(document number A5E00434623).
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......