16-Channel, 24 VDC Power Supply MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
275
22.8
Technical Specifications
Technical Specifications: 16-Channel, 24 VDC Power Supply MTA
(6ES7650-1BE10-3XX0)
Dimensions
- See Section 1, Figure 1.3, Short Version
Mounting
DIN Rail
35mm (deep top hat style)
Orientation
horizontal or vertical
Power Input
Voltage Input for Single or Redundant Feed
21.6 to 28.8 VDC
Total current
to 40
o
C
8.1 A maximum
to 60
o
C
5.1 A maximum
without load
0.1 A maximum
Power Dissipation (typical)
5W
Power Output per channel
Output voltage
min L+ - 1.2V
Output current
0.5A
Short circuit protection
yes, electronic
•
Threshold
ca. 1A
Wiring two or more outputs of the same MTA in
parallel for increased performance
supported
Wiring two or more outputs of different MTAs in
parallel for increased performance
not supported
Power Output per module
Output current
Total 8A max at Ta = 40
o
C
Total 5A max at Ta = 60
o
C
Power Monitoring System - Output Contact Ratings
Threshold voltage
ca. 15 V
Maximum switched Voltage
30 V DC
Maximum switched Current
0.5 A resistive load; not short circuit
protected
Short Circuit Detection - Output Contact Ratings
Maximum switched Voltage
30 V DC
Maximum switched Current
0.5 A resistive load; not short circuit
protected
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......