8-Channel HART Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
259
20.8
Changes to Module Specifications
Changes to 8-Channel HART Analog Input Module (6ES7 322-7TF01-0AB0) Specifications
when used with 8-Channel HART Analog Input MTA (6ES7 650-1AA61-2XX0)
Redundant Mode
When using the MTA, the I/O module must be
used in the redundant mode. For more
information see Section 2.4
Connecting
sensors/actuators in redundant mode
in the
HART analog modules manual, 08/2007,
A5E00434623-03.
±20 mA input range
The ±20 mA input range can not be used.
Combining 2 wire and 4 wire transducers on one
module.
Any combination of 2 wire and 4 wire
transducers is possible.
The module inputs must be configured as 4
wire transducers regardless of transducer
type.