16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
243
Technical Specifications: 16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA (6ES7650-
1AM30-3XX0)
Insulation test
Rated voltage 150V < Ue < 300V
Rated voltage 100V < Ue < 150V (reinforced)
Rated voltage 300V < Ue < 600V
Test voltage (routine test at IEC 61131-2)
1350 VAC/2sec (all channels to sec.+ shield)
820 VAC/2sec (between channels for 150 VDC)
2200 VAC/2sec (Group 0 < -- > Group 1)
Relay
Maximum Relay Contact Ratings
Resistive Load:
Max Switched Current:
5 Amps at 120 VAC – 230VAC
5 amps at 24 VDC
0.4 A at 150 VDC
UL Contact Ratings:
5A/250 VAC General Purpose
(Siemens Spare P/N A5E02164559)
Switching Frequency
Resistive load max. 0.1Hz
Coil Resistance
1440 Ohms (Nominal)
Minimum Output Rating (Wetting Rating)
100 mA at 12 VDC
Relay Output Fuse
None - External Fusing required
Minimum operations
Mechanical
30 million operations
Electrical
2 x 10
5
at 10 A, 250 VAC, cosφ=0.6, 70°C
Relay Contact Restrictions
Relay Contact Fusing
Fuses for the relay output connection must be
provided externally to the MTA
Relay Contact Protection
To extend the life of the relay contacts
protection components should be used. The
protection components depend on the load
voltage (ac or dc) and the load characteristics
(high current, inductive, etc.)
Relay Voltage Restrictions
For voltages up to 150 VDC channels may be
different voltages (one channel SELV and next
max. 150 VDC).
For voltages greater than 150 VDC, all
channels must be of the same voltage.
For AC voltages all channels must be the same
phase for the channels in one group. There can
be different phases between groups.
* Limiting the signal wiring to 14 AWG / 2.1 mm
2
will make it easier to assemble and remove the
MTA cover.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......