Installation
Marshalled Termination Assemblies for ET200M Remote I/O Modules
32
A5E00482820-12
2.3
Installation Procedure
2.3.1
Without Cover and Frame
Step
Action
1
Mount the MTA to the DIN rail (Recommend 35mm x 15mm Top Hat style)
2
For EMC Compliance connect the MTA Shield stud to earth ground.
3
Plug the interconnecting cable into the PCS7 I/O Modules
4
For analog I/O Modules: Install shield connecting element, strip a section of outer
insulation from interconnecting cable and place in shield connecting element
5
Plug the interconnecting cable into the D25 or D50 on the MTA
6
Plug the Field terminal connectors into the MTA
7
Plug the IO power connector into the MTA
8
Apply power
2.3.2
With Cover and Frame
Refer to Figures 1-2 and 2-1
Step
Action
1
Mount the MTA to the DIN rail (Recommend 35mm x 15mm Top Hat style)
2
Remove cover using screw driver to disengage the cover retaining tabs from cover.
3
For EMC Compliance remove the Shield Stud Break-Away Tabs (Fig 1-2) on the
frame adjacent to the shield stud to connect the MTA Shield stud to earth ground.
4
Plug the interconnecting cable into the PCS7 I/O Modules.
5
For analog I/O Modules: Install shield connecting element, strip a section of outer
insulation from interconnecting cable and place in shield connecting element.
6
Plug the interconnecting cable into the D25 or D50 on the MTA. Remove the
Module 2 Break-Away Connector Cover (Fig 2-1) to access the connector for module
2 for redundant configurations.
7
Plug the Field terminal connectors into the MTA.
8
Remove the Power Connection Break Away Tabs (Fig 2-1) on the frame adjacent to
the power connection and plug the IO power connector into the MTA.
9
If the Power Monitor Board is used, remove the Power Monitor Break-Away Tabs
(Fig 2-1) on the frame adjacent to the Power Monitor Board connector and connect
to the Power Monitor Board.
10 Snap cover into place
11 Apply power
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......