6-Channel F Analog Input HART MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
143
Figure 11–3 2-wire transducer supply test setup
Connector MODULE 1
Connector MODULE 2
150 Ohm
150 Ohm
FAIH MODULE 1
FAIH MODULE 2
MTA - FAIH
6.2 V
5.6 V
2-wire
supply
2-wire
transducer
+
-
+
-
L+
PWx
Ix+
M
24V
Power supply
Current
indicator
Ix-
The correct function of the 2-wire transducer supply can be checked without
modifying the wiring.
A DC current indicator connected with the minus connector to ground (M/A or M/B)
contacts PW0 … PW5.
Measured current must be 35mA … 40mA.
In case a smaller value will be measured the MTA has become defect.