6-Channel F Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
112
A5E00482820-12
9.16.4
FAI MTA to SAI MTA Cable
The FAI MTA to SAI MTA Input Sharing cable uses only 13 conductors. The FAI
Channel 0 to Channel 5 input signals have been mapped to Channels 0 through 5
on the SAI MTA. Channels 6 & 7 of the SAI can be used for other inputs. The cable
connections can be seen in the table below.
The FAI MTA to SAI MTA Input Sharing cable is custom manufactured on a project
basis. See the project manager to for more information.
The assembly view of the cable can be seen in Figure 9–17.
Table 9–1 FAI MTA to SAI MTA Cable
FAI Channel
FAI MTA
Signal
FAI MTA
D50M Pin
SAI MTA
Field
Terminal
SAI MTA
Signal
SAI Channel
CH 0+
I0R+
19
TB1 PIN 2
I0+
CH 0+
CH 0-
I0-
27
TB1 PIN 3
I0-
CH 0-
CH 1+
I1R+
20
TB1 PIN 6
I1+
CH 1+
CH 1-
I1-
28
TB1 PIN 7
I1-
CH 1-
CH 2+
I2R+
38
TB1 PIN 10 I2+
CH 2+
CH 2-
I2-
46
TB1 PIN 11 I2-
CH 2-
CH 3+
I3R+
23
TB1 PIN 14 I3+
CH 3+
CH 3-
I3-
47
TB1 PIN 15 I3
CH 3-
CH 4+
I4R+
40
TB2 PIN 2
I4+
CH 4+
CH 4-
I4-
15
TB2 PIN 3
I4-
CH 4-
CH 5+
I5R+
8
TB2 PIN 6
I5+
CH 5+
CH 5-
I5-
16,17, 32
TB2 PIN 7
I5-
CH 5-
Shield
Shield
TB1 PIN 4
SH0
5
The shield connection to the SAI MTA is optional and should be investigated for safe
operation before use
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......