8-Channel TC Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
83
8.8
Module Restrictions
Restrictions for 8-Channel TC Input MTA
(6ES7650-1AF51-2XX0 or 6ES7650-1AF50-2XX0)
I/O Module Restrictions
MTA Design
External Junction Compensation only
Module Accuracy
External Compensation Accuracy
+/-0.3C or 0.6% of terminal temperature
8.9
Typical Thermocouple Connection to Field Terminals
Figure 8–2 Typical Thermocouple Connection to Field Terminals
TC+3
TC-1
TC-0
SH0
TC+1
THERMOCOUPLE
TC+0
SH2
TC-2
TC-3
SH3
TC+2
SH1
TB1