6-Channel F Analog Input HART MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
124
A5E00482820-12
Note
When using a 1.5A channel fuse it is possible that one or more of the zener
diodes on the two Zener Diode Boards may be damaged in the event of a short
circuit in the field. It is recommended that the diode boards be tested or replaced
in the event a 1.5A channel fuse opens.
Note
Fuses are available as spare parts from Siemens.
Fuse information can be found at:
http://www.littelfuse.com
http://www.bussmann.com
10.8
Changes to the Technical Specifications for 6-Channel
F ANALOG INPUT HART Module
(6ES7 336-4GE00-0AB0)
This section contains changes to the I/O module specifications when it is used with the MTA.
Changes for 6-Channel F Analog Input HART MTA
(6ES7650-1AH61-5XX0)
Transmitter Connections
Only 1 transmitter can be connected to a
channel.
Output voltage for 2 wire transducer and cable
with 22 mA transducer current
14 V @ 24 V Supply*
Fail-safe Performance Characteristics
Adds a dangerous undetected failure rate (2.4
FIT for 6 channels) to the FAI module in any
configuration.
Sensor Supply
The FAI module internal sensor supply
outputs are not used when using the FAIH
MTA.
Protection against short circuit with external
sensor supply
No external fuse required. The FAIH MTA
limits current.
* If the output voltage is not sufficient for a 2 wire transmitter, safety barrier and field wiring, it is
recommended that a 4 wire transmitter be used.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......