16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
242
A5E00482820-12
18.7
Technical Specifications
Technical Specifications: 16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA (6ES7650-
1AM30-3XX0)
Dimensions - See Section 1, Figure 1.3, Long Version
Mounting
DIN Rail
35mm ( deep top hat style)
Orientation
horizontal or vertical
Power Input
Voltage Input for Single or Redundant Feed
21.6 to 28.8 VDC
Current Consumption (nominal ratings)
All Channels Active
0.71 A Typical
Power Dissipation (typical)
9 W
Wire Size – US / Metric
24 to 14 AWG / 0,205 – 2,08 mm sq.
Fuse Ratings
Module
2.0 A (Bussmann P/N: GMA-3.0A)
(Siemens Spare P/N: A5E01574387)
Environmental
Ambient Temperature
-25C to +60C
Humidity
5% to 95% Non-condensing
Approvals
MTA Agency Approvals
See Preface section, Approvals Table
Indicators
Input Power
Green LED on when input power available, Red
LED on when power polarity is reversed
Module Power
Green LED on when module power available
Channel Status
Green LED on when channel is ON
Field Connections
Output Contacts
Normally Open – NO
Common – C
Normally Closed – NC
Wire Size – US / metric
24 to 14 AWG
Wire Size – Metric
0,205 – 2,08 mm sq.*
Isolation
between channels < -- > secondary
Yes (250 VAC)
between the channels
yes. U< =150V reinforced insulation
U > 150V to 250V basic insulation
permissible voltage between groups of 8 channels 500 VAC (basic insulation)
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......