16-Channel, 24 VDC Power Supply MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
271
22
16-Channel, 24 VDC Power Supply MTA
Part No. 6ES7650-1BE10-3XX0
22.1
Description
This section contains information and requirements to facilitate installation of
Siemens Marshalled Termination Assembly (MTA) (6ES7650-1BE10-3XX0),
designed to energize 4-wire transducers
22.2
Features
The following features have been incorporated into this MTA:
•
Redundant power connections
•
LED indication of redundant power supply operation
•
LED indication of reverse polarity
•
Power monitor output
•
Short circuit detection on the outputs
•
16 outputs rated at 24V/ 0.5A
•
each output electronically short circuit protected
•
one LED per output
•
Shield connections available for channel cabling
•
Ground stud for connecting shield to earth ground
22.3
Operation
The modules
8-Channel Analog Input MTA (6ES7 650-1AA52-2XX0)
6-Channel F Analog Input HART MTA (6ES7 650-1AA62-5XX0)
8-Channel Analog Input HART MTA (6ES7 650-1AA61-2XX0)
provide a supply only for 2-wire- and not for 4-wire transducer.
This gap will be filled by the 16-Channel Power Supply MTA. The MTA provides 16
outputs rated at 24V/0.5A. In case 0.5A is not sufficient for energizing the
transducer, two or more outputs of the same MTA can be connected in parallel.
The outputs are individually short circuit protected without using destructible fuses.
In case one or more outputs are short circuited, there is no influence on the
remaining outputs.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......