
Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
230
A5E00482820-12
17.9 Module Restrictions
Note
Module restrictions differ slightly for the two MTA part numbers. Note the part
number and refer to the appropriate sections below.
17.9.1
Module Restrictions for 6ES7650-1AM30-6XX0
Restrictions for 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
(6ES7650-1AM30-6XX0)
I/O Module Restrictions
Module Design - Diode Outputs used
See module specifications for limitations
Relay
Maximum Relay Contact Ratings
Resistive Load:
Max Switched Power: 150 W 0r 1250 VA
Max Switched Current:
5 Amps at 120 VAC – 230 VAC
5 Amps at 24 VDC
0.4 A at 120 VDC
¼ HP @ 120 VAC motor load
Coil Resistance
1200 Ohm (Nominal)
Minimum Output Rating (Wetting Rating)
0.1 A at 5 VDC
Relay Output Fuse
None - External Fusing required
Minimum operations
Mechanical
30 million operations
Electrical
1 x 10
5
at 10 A, 24 VDC or 120 VAC
2 x 10
5
at 8 A, 230 VAC
Relay Contact Restrictions
Relay Output Fusing
Fuses for the relay output connection must be
provided externally to the MTA
Relay Voltage Restrictions
For voltages up to 150 VDC channels may be
mixed mode.
For voltages greater than 150 VDC, all
channels must be of the same voltage.
For AC voltages all channels must be the
same phase.
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......