16-Channel, 24 VDC Discrete Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
200
A5E00482820-12
Key to numbered items in Figure 15–1:
Item
Description
7
Module power indicators (Module 1, Module 2)
8
Channel status indicators (1 of 16)
9
Heatsink
10
Connector for Power Monitor Board
11
Ground stud for connecting shield to earth ground
15.8
Technical Specifications
Technical Specifications: 16-Channel, 24 VDC Discrete Output MTA
(6ES7650-1AD10-2XX0)
Dimensions
- See Section 1, Figure 1.3, Short Version
Mounting
DIN Rail
35mm (deep top hat style)
Orientation
horizontal or vertical
Power Input
Voltage Input for Single or Redundant Feed
21.6 to 28.8 VDC
Current Consumption (nominal ratings)
All outputs ON, maximum loads
8.3 A maximum
All outputs OFF
0.26 A maximum
Power Dissipation (typical)
10 W
Fuse Ratings
Module
10 A/125V (Bussmann P/N: GMA-10A)
(Siemens Spare P/N: A5E01568881)
or (Schurter P/N: 0034.1526)
(Siemens Spare P/N: A5E01574409)
Environmental
Ambient Temperature
-25C to +60C
Humidity
5% to 95% Non-condensing
Approvals
MTA Agency Approvals
See Preface section, Approvals Table
Indicators
Input Power
Green LED on when input power available,
Red LED on when power polarity is
reversed
Module Power
Green LED on when module power
available
Channel Status
Green LED on when channel is ON
Field Connections
Wire Size – US / metric
24 to 14 AWG / 0.2 to 2.08 mm
2
Summary of Contents for ET 200M
Page 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Page 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Page 26: ......
Page 136: ......
Page 166: ......
Page 196: ......
Page 236: ......
Page 252: ......
Page 278: ......