Ethernet TCP/IP Gateway
Configuration via web server
In order to configure the Auto Update Mode via web server, perform the following configu-
ration steps:
Open a web browser on a PC in the network and go to the address of the UE410-EN.
Click
Ethernet TCP/IP Interface Configuration
on the UE410-EN homepage.
Click
Socket
N
to edit any of the four socket interfaces.
Select the data sets which shall be included in the TCP/IP message by checking the
respective Checkbox
Enable Data Set N
.
These data sets will be sent to the application whenever a change is detected and, if
Enable Heartbeat Message is enabled, at least as often as the specified Heartbeat
Update Rate.
Select
Enable Heartbeat Message
if the selected data set(s) shall be constantly sent
on a specified rate (whether the content has changed or not).
Set the
Heartbeat Update Rate
to the required value.
The Heartbeat Update Rate specifies the update interval in milliseconds with which the
data sets are updated to the application. Standard = 5000 ms, Minimum = 200 ms,
Maximum = 65535 ms. Any value entered less than 200 ms will be increased to
200 ms.
Activate
Save in Flash
and click
Submit
to save the selection or continue configuration.
If Heartbeat Message has been enabled but no data set is selected (e.g. none of the
Checkboxes
Enable Data Set N
is checked), the UE410-EN will not send any Auto Update
TCP/IP messages and remain in Polling Mode.