Flexi Classic gateways
3.2.18
SW-VERSION_H and SW-VERSION_L
High byte/low byte for the software version for the selected Flexi Classic module.
The software version is supplied as a 16-bit-hex number, e.g. 0624 = 2006, week 24.
Bit 7
6
5
4
3
2
1
Bit 0
SW-VERSION H
SW-VERSION L
3.2.19
FUNCTION
FUNCTION describes the setting of the rotary switch on the selected Flexi Classic module
(not UE410-GU). This byte is to be interpreted differently depending on the module type,
e.g. as program switch, switch for off delay or function switch.
Bit 7
6
5
4
3
2
1
Bit 0
UE410-MU
UE410-XU
FUNC
TIME
UE410-MM
UE410-XM
FUNC A
FUNC B
UE410-8DI
INPUT A
INPUT B
UE410-MDI
FUNC C
–
FUNC
Program switch
UE410
F
MU/UE410
F
XU
0 = Invalid
1-8 = Function 1 to 8
9 = Invalid
FUNC A
See description UE410-MM/UE410-XM
FUNC B
See description UE410-MM/UE410-XM
FUNC C
See description UE410-MDI
TIME
Reactivation delay UE410-MU/
UE410-XU. The value defines a
factor that must be multiplied with
the time variant T from KONF to
obtain the reactivation delay in sec.
0 = Factor 0
1 = Factor 0.5
2 = Factor 1
3 = Factor 1.5
4 = Factor 2
5 = Factor 2.5
6 = Factor 3
7 = Factor 3.5
8 = Factor 4
9 = Factor 5
INPUT_A
Input circuit function group A
UE410-8DI
0 = Not used
1-9 = Function 1 to 9
INPUT_B
Input circuit function group B
UE410-8DI
0 = Not used
1-9 = Function 1 to 9
Tab. 22: SW-VERSION_H and
SW-VERSION_L
Tab. 23: FUNCTION