PROFINET IO Gateway
Select
Return Only Enabled Data
and click the desired parameters in the list if the
length of the data set shall be reduced to the effective data only. Example:
In order to use these settings temporarily do not check
Save in Flash
and click
Submit
.
In order to use these settings permanently, check
Save in Flash
and click
Submit
. The
configuration is then saved in the non-volatile memory of the UE410
F
EN and is still
available after the gateway has been restarted.
If the option
Return Only Enabled Data
is activated in the configuration of the data set,
the data set can have a different length depending on the compilation. The maximum
length is 124 bytes. The minimum length is 0 (no data selected). This must be taken
into account in regards to the size of the record read in the PLC.
The selected data are transferred for
all
Flexi Classic modules respectively. The data
are zeroed for modules that do not exist.