Flexi Classic gateways
ErrCode for ErrClass 0Ah:
For base module
M
01
Logical error in input group A
M
10
Logical error in input group B
M
11
Logical error in input groups A and B
M
02
Logical error in the start function group A
M
20
Logical error in the start function group B
M
22
Logical error in the start function groups A and B
M
08
Logical error in the bypass function group A
M
80
Logical error in the bypass function group B
M
88
Logical error in the bypass function groups A and B
For muting master/slave:
M
01
Logical error in input group A
M
10
Logical error in input group B
M
11
Logical error in input groups A and B
M
02
Logical error in the start function group A
M
20
Logical error in the start function group B
M
22
Logical error in the start function groups A and B
M
04
Logical error in the output function group A
M
40
Logical error in the output function group B
M
44
Logical error in the output function groups A and B
M
08
Logical error in the bypass function group A
M
80
Logical error in the bypass function group B
M
88
Logical error in the bypass function groups A and B
(M = Bit mask; several errors can occur at the same time)
On the occurrence of error codes other than those listed here, please contact the SICK
technical hotline.
3.2.17
MOD-ID
Module identifier for the selected Flexi Classic module (not UE410-GU).
Bit 7
6
5
4
3
2
1
Bit 0
MOD-ID
MOD-ID
Module identifier
1 = UE410-MU
2 = UE410-XU
3 = UE410-8DI
4 = UE410-MM
5 = UE410-XM
6 = UE410-MDI
Note
Tab. 21: MOD-ID