Chapter
3
Operating Instructions
Flexi Classic Gateways
14
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
8011834/YT28/2016-03-15
Subject to change without notice
Flexi Classic gateways
3.2.4
BAS1
Group error bits on the overall system and output data on the UE410-MU, UE410-MM and
UE410-GU.
Bit 7
6
5
4
3
2
1
Bit 0
UE410-MU
UE410-MM
QS
AF
ZF
RO
X1/2
X3/4
UE410-GU
IF
–
–
–
–
FM
Q1
Q2
IF
Internal error
0 = No internal errors
1 = An internal error has occurred on one of the
Flexi Classic modules
QS
Cross circuit error
(not on UE410-GU)
0 = No cross circuit error
1 = Cross circuit error detected on an input pair
on the overall system
AF
Process error
(not on UE410-GU)
0 = No process error
1 = A process error has occurred on one of the
Flexi Classic modules in a safety circuit
ZF
Time error
(not on UE410-GU)
0 = No time error
1 = An internal error has occurred on one of the
Flexi Classic modules
RO
EDM contacts open
(not on UE410-GU)
0 = No EDM error
1 = An error has occurred on the EDM contacts
on one of the modules. EDM contact was open
FM
Program or function switch changed 0 = Switches have not been actuated
1 = Switches have been changed during
operation
X1/2
Outputs Q1/Q2
UE410-MU/MM
0 = Q1/Q2 inactive
1 = Q1/Q2 active
X3/4
Outputs Q3/Q4
UE410-MU/MM
0 = Q3/Q4 inactive
1 = Q3/Q4 active
Q1
Output Q1
UE410-GU
0 = Q1 inactive
1 = Q1 active
Q2
Output Q2
UE410-GU
0 = Q2 inactive
1 = Q2 active
3.2.5
BAS2
Output data from the A/B function groups on the UE410-XU main module, the UE410-8DI
expansion modules and the UE410-XM, UE410-MDI muting modules.
Bit 7
6
5
4
3
2
1
Bit 0
MOD2
MOD3
MOD4
MOD5
Tab. 5: BAS1
Tab. 6: BAS2