DeviceNet Gateway
Display
Meaning
PWR (green)
Supply voltage present
NS (off)
“DUP MAC Check” not completed successfully.
NS (green flashing)
UE410-DEV operating on the bus, but has not yet been detected by a
master or no logical connection has been established to the UE410-
DEV.
NS (green)
UE410-DEV has been detected by a master and a logical connection
has been established to the UE410-DEV.
NS (red)
During “DUP MAC Check”, UE410-DEV has found a different device
with the same MAC ID.
MS (green flashing)
The fieldbus connection has been interrupted. The remote PLC is in
the stop mode. The master is currently attempting to establish the
connection to the UE410-DEV. The planned I/O size in the scan list is
incorrect (Error 77 on the scanner).
MS (green)
UE410-DEV is ready and the PLC is in the Run mode.
MS (red flashing)
The internal EEPROM has an error.
Display
Meaning
X 10
Address switch 1 (possible bus addresses 0-63)
10-position rotary switch for setting the module address (tens)
X 1
Address switch 2 (possible bus addresses 0-63)
10-position rotary switch for setting the module address (units)
DIP switch
4-pole DIP switch for setting the baud rate
DIP 3 and 4 are not used.
If a larger address is selected, address 63 is active.
The occurrence of random or systematic errors in the gateway or in its operation does
not result in the degradation of the safety functions on the Flexi Classic system.
With the operating voltage switched on, no gateways are allowed to be disconnected
from the Flexi Classic system or added by plugging in.
The DeviceNet master cannot overwrite the address set.
A modified address setting only becomes effective after switching off and switching on
the Flexi Classic system.
6.1.3
Application diagnostic outputs UE410-DEV
Assignment
Description
X1-X4
Short circuit and overload detecting control outputs (PNP) supplied via Flexi
Classic system
Tab. 56: Indication LED
UE410-DEV
Tab. 57: Address switch
UE410-DEV
Notes
Tab. 58: Application
diagnostic outputs