![SICK Flexi Classic Operating Instructions Manual Download Page 31](http://html.mh-extra.com/html/sick/flexi-classic/flexi-classic_operating-instructions-manual_1264300031.webp)
Operating Instructions
Chapter
4
Flexi Classic Gateways
8011834/YT28/2016-03-15
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
31
Subject to change without notice
PROFIBUS DP Gateway
Design variant 4 is shown in the following table.
Data direction
I/O modules
GSD identifier
Read
Write
CRC1 DIG-OUT
CRC2 REQ-ID
BAS1 Reserved
SCB1 Basic1 4 Byte in/out
Contains configuration checksum
and basic diagnostics
ID: 33h (mandatory)
BAS2 Reserved
BAS3 –
SCB2 Basic2 2 Byte in
Contains extended basic diagnostics
ID: 11h (optional)
BAS4 –
B1 –
B2 –
:
:
DIAG 10 Byte in
Depending on the REQ-ID this
module contains
10 bytes diagnostics with varying
content
ID: 19h (optional)
B10 –
MED1 –
MED2 –
:
:
MED 13 Byte
Contains the input signals for all Flexi
Classic modules fitted
E.g. MED7 contains the input data
for module 7
ID: 1Ch (optional)
MED13 –
See also section 3.2 “Status information of all Flexi Classic gateways (system bytes)”.
If a DP master is used that does not send any planning data to the UE410-PRO (e.g.
PROFIBUS Master Simulator PR-MSV01 (6022458) from SICK in the “Start without GSD
file” mode), the UE410-PRO supplies the diagnostic data as for plan 5 (see Tab. 34 on
page 30).
4.2.2
Documenting with PROFIBUS-DP Master Simulator
You can save diagnostics data on a PC with the aid of the PROFIBUS-DP Master Simulator
(see section 11.7 “Accessories/spare parts”) and the file flexi_config_list.xls.
For this purpose, connect a data cable between PC, PROFIBUS-DP Master Simulator and
UE410-PRO (RS-232-D-Sub). Install the file “flexi_config_list.xls” on your PC, Excel 2000 or
later must be installed on the PC.
You can then save and document the diagnostics data and settings for the overall system
with the aid of your PC.
We also refer you to our homepage on the Internet at
There you will find the following files for download:
GSD file
flexi_config_list.xls
4.2.3
Diagnostics data UE410-PRO
You will find the description of the status bytes in the section “Status information of all
Flexi Classic gateways (system bytes)”.
Tab. 35: Format of the diag-
nostics data UE410-PRO