8
Parameters
Overview of parameters
Operating Instructions – Compact Extra-Low Voltage Drives
57
8
Parameters
The compact extra-low voltage drive comprises a parameterizable power section with
integrated controller. The motor-specific parameters are already preset to the optimum
settings in a delivery state. Startup is restricted to the application-specific parameters.
These can be adapted to the requirements of the application by using the DCAShell
engineering software.
8.1
Overview of parameters
8.1.1
Parameters that can be changed
INFORMATION
• In delivery state, the various parameters are pre-parameterized with the values in
the "Factory setting" column. You can restore the factory settings by using the
DCAShell engineering software.
• The values that are designated with "Application" in the table are used to adapt to
application-specific variables. Set these values during startup.
• The values that are designated with "System" in the table are used to specify the
motor-specific properties. Only modify these values after consultation with trained
experts.
• You can read the parameter values via the DCAShell engineering software during
operation or in an idle state. Only change the parameter values if the drive is in an
idle state and the output stage has been inhibited/de-energized.
The following parameters are available:
No. Parameters
Unit
Factory set-
ting
Min.
Max.
Class
Explanation
0x1 Mode 1
1
0
9
System
Application selection
0x2 Mode 2
1
0
8
System
0x3 Out 1
9
1
9
System
Standard: Brake
control
0x4 Out 2
6
1
8
Application
Standard: Position
window reached
0x5 Out 3
5
1
8
System
Standard: Ready for
operation
0x6 Restart
1
0
1
System
0x7 Reserved
0
0
65535
0x8 Reserved
0
0
65535
0x9 Reserved
0
0
65535
0xA Reserved
0
0
65535
0xB FE_Speed_X1
Digits
0
0
1023
System
0xC FE_Speed_X2
Digits
1023
0
1023
System
0xD FE_Speed_X3
Digits
1023
0
1023
System
0xE FE_Speed_Y0
min
-1
500
-30000 29999 System
Speed A1/N4
26718014/EN – 11/2020