Startup
Parameterizing the analog setpoint
Operating Instructions – Compact Extra-Low Voltage Drives
50
6.5.4
Hysteresis
Additionally, you can set a hysteresis for X1, X2, and X3 under "Extended parame-
ters". The following diagram provides an example. In this case, a hysteresis value of
2
V
(205
digits) is defined for X2. The value stands for the hysteresis width on the X-
axis. The value is used by one half underneath the associated curve point and by the
other half above it. In the example, the hysteresis range is between
4
V and
6
V
(5 V ± 1 V). You find the associated parameters in the table.
1000
3000
4000
2000
1
2
3
4
5
6
7
8
9
10
min
-1
V
30636129291
No.
Parameters
Value
Unit
0xB
Speed characteristics_X1
0
Digits
0xC
Speed characteristics_X2
511
Digits
0xD
Speed characteristics_X3
1023
Digits
0xE
Speed characteristics_Y0
0
min
-1
0xF
Speed characteristics_Y1
0
min
-1
0x10 Speed characteristics_Y2
2000
min
-1
0x11 Speed characteristics_Y3
4000
min
-1
0x12 Speed characteristics_Y4
400
min
-1
0x13 Speed characteristics_X1_Hysteresis
0
Digits
0x14 Speed characteristics_X2_Hysteresis
205
Digits
0x15 Speed characteristics_X3_Hysteresis
0
Digits
26718014/EN – 11/2020