The 'free-hanging' un-supported weight of cables should not exceed the
weight of the unit.
Figure 7-5: Transmitter unit mounting arrangement (example shown with adjustable
mount)
1
Analyzer mounting flange
2
Adjustable mount flange
3
Process flange
4
Process flange reinforcement plate
5
Process wall
Transmitter Unit =
2.0 kg (4.4 lb.)
Flange =
3.5 kg (7.7 lb.)
Unsupported cable weight =
3.5 kg (7.7 lb.)
Total =
9.0 kg (19.8 lb.)
If the process wall is not strong enough to support the TU or RU, Servomex
recommend that you use a reinforcement plate.
Note:
It is your responsibility to assess and design the reinforcement plate that you will
use in your installation, subject to local conditions.
This reinforcement plate could be part of the process flange (as shown in diagrams)
or a separate reinforced section of the process wall.