- 60 -
5-5
Special Functions
5-5-4
Alarm Contents Reading Operation
Alarm history record display is a function for displaying alarms occurred in the past.
The latest 5 alarms will be recorded. If a new alarm occurs, then the first alarm will be deleted.
Operation example: reading alarm contents
Operation
Display
Description
Select function code F1805 (Reading alarm data)
or
(press)
Press the (Set) key or quick knob, then the set value of
function code will be displayed.
Turn the quick knob to select 1, then if F1805 = 1, the alarm
contents will be read.
Press the (Set) key to execute the alarm reading function.
Alarm history record number and alarm contents are
alternately displayed, and will be displayed if there is
no alarm record.
Turn the quick knob, the alarm displayed will be shifted
continually. In alarm history record, the alarm with the
smallest number is the latest alarm.
or
Press the
(Back) key or key, then the interface will
return to function code value setting.
or
Press the
(Back) key or key to return to function code
selection interface.
When the set function code F1805 = 9, then the alarm history record can be deleted.
or
or