Description of Functions
Example)
When operation timer T2 is running and the frequency is changed on the operation panel, make an
acceleration/deceleration according to the changed frequency, enter the changed frequency values
in to F1202.
Note
2:
Since the simple scheduled operation will specify multi-speed frequency in each timer, the multi-speed
changes made for control circuit input terminals will be noneffective.
7) Cycle completion signal of simple
scheduled
operation
If a control terminal output function is set in cycle completion of simple
scheduled
operation (any one of
F1509
-
F1511 is 3), before the operation timer T0 stops the inverter or enters into DC braking and braking
excitation, the open-circuit output of collector between control circuit output terminal and DCM1 & 2 is set to
ON and is about 200ms. Please put the external action command to OFF after one cycle is completed, or use it
when peripheral equipments and the programs are required to be synchronized.
Note
1:
There is an output when the cycle completion signal of simple scheduled operation passes the T0. When an
output is not wanted, make a setting beyond F1509
-
F1511=3, or set the operation timer T0 to 0.0s.
Note
2:
On the last operation timer when the total cycle (simple scheduled operation
repetition count) is completed,
when the inverter stops or starts DC braking and braking excitation, the cycle completion signal which has
no relationship with the timer status will be ON.
1 cycle
Deceleration Stop
Inverter stops or
under DC braking and braking excitation
When free run stops
When deceleration stops, DC braking stops
and braking excitation stops
8) Figure of simple
scheduled
operation and function code setting
The following figure summarizes the correspondence between the actions of simple
scheduled
operation and the
function codes.
Operation timing T0
-
T15: F2203
-
F2217=0
-
65000s
Multi-speed frequency 1
-
15: F2101
-
F2115=0
-
599Hz
Forward/reverse, acceleration/deceleration time: F2221
-
F2235
Repetition count: F2202=0
-
250 (0: without limit)
Fr
eq
u
en
cy
Output terminal DO1
~
3
Various relay output
about 200ms
about 200ms