- 140 -
7-3
Description of Functions
F1319
Functions corresponding to high altitude areas
In high altitude areas, due to the unit cooling capacity, the current derating rate of parts and other reasons, it is
recommended to use larger inverters by one rank
.
However, when used in high-altitude areas of more than 1,000m above
sea level, the rated current can be derated, and this function should be used for selecting suitable altitude where
applicable.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1319
Functions corresponding to
high altitude areas
1: 1,000m or below
2: 1,000-1,500m or below
3: 1,500-2,000m or below
4: 2,000-2,500m or below
5: 2,500-3,000m
1
1
●
The current derating rate of inverter for each altitude range is as shown below.
Content
Current derating rate
1,000m or less
1
1,000 - 1,500m or below
0.966
1,500 - 2,000m or below
0.925
2,000 - 2,500m or below
0.900
2,500-3,000m
0.876
F1320
Rating selection
A function which changes the rating to mode A for heavy overload or mode B for light overload.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1320
Rating selection
1: Mode A (heavy overload)
2: Mode B (light overload)
1
1
●
Mode A (heavy overload) allows an overload capacity of 150% per minute.
●
Mode B (light overload) allows an overload capacity of 120% per minute.
Note: If the mode is switched by specification selection, then the relevant function codes shall be initialized.
e.g.
) F1009, F1701, F1704, F5001, F6001 and F6102.