- 150 -
7-3
Description of Functions
The methods of conversion between output values of possible output analog signal from AOUT1 or AOUT2 terminal and
actual values are shown in the table below.
F1501
F1504
Set value
Output signal content
Conversion method
0
No function
1
Set frequency [Hz]
120Hz/10V
2
Output frequency [Hz]
120Hz/10V
3
PID1 feedback value [Hz]
120Hz/10V
4
PID2 feedback value [Hz]
120Hz/10V
5
Output current [A]
*
1
6
Output voltage [V]
500V/10V
7
DC voltage [V]
500V/5V
8
Radiator temperature [
℃
]
100
℃
/8V
9
Load factor [%] (integral value of the
electric thermistor)
100%/5V
10
Load factor [%] (ratio to rated current)
100%/5V
11
VIF1 analog input value [V]
4-20mA current input
,
20mA/10V
0-5V voltage input
,
5V/5V
0-10V voltage input
,
10V/10V
12
VIF2 analog input value [V]
13
VIF3 analog input value [V]
14
Speed [rpm]
1,800rpm/5V
15
Active power [kW]
*
2
16
Apparent power [kVA]
*
3
17
PID1 command value [Hz]
120Hz/10V
18
PID1 input deviation value [Hz]
120Hz/10V
19
PID2 command value [Hz]
120Hz/10V
20
PID2 input deviation value [Hz]
120Hz/10V
24
External PID1 output value [Hz]
120Hz/10V
25
External PID2 output value [Hz]
120Hz/10V
35
Command frequency [Hz]
120Hz/10V
36
Command torque [%]
400%/10V(
※
1)
40
Output torque [%]
400%/10V(
※
1)
※
1 The positive and negative values of torque are output with
5V
as the center.
(0V=-200%, 5V=0%, and 10V=200%)
Note
1:
Maximum allowable current: 15mA.
(But, the converted value is no-load output voltage. If the output current increases, the output voltage will decrease.
In this case, the signal output can be adjusted using output coefficient.)