- 144 -
7-3
Description of Functions
F1413
ES input terminal function
This function can be used for switching the function of control input terminal ―ES‖.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1413
ES input terminal function
1: NO external thermistor signal
2: NC external thermistor signal
1
1
The function shall be switched according to the contact type.
F1413=1: ES terminal (external thermistor input terminal) is connected with an NO (normally open) contact.
F1413=2: ES terminal (external thermistor input terminal) is connected with an NC (normally closed) contact.
F1414
Selection of input terminal DI1
F1415
Selection of input terminal DI2
F1416
Selection of input terminal DI3
F1417
Selection of input terminal DI4
F1418
Selection of input terminal DI5
F1419
Selection of input terminal DI6
F1420
Selection of input terminal DI7
F1421
Selection of input terminal DI8
These functions are used to assign functions to the digital multifunctional input terminals DI1 - DI8 arbitrarily through
data selection.