- 206 -
7-3
Description of Functions
Code No.
Function Name
Date Content
Setting
Resolution
Factory
Presets
3119
Frequency corresponding to PID2
control maximum command value
0-600Hz
0.01Hz
60
3123
PID start mode selection
1
:
Direct input mode
2
:
Conditional input mode
1
1
3124
PID end mode selection
1
:
Direct input mode
2
:
Conditional input mode
1
1
3125
PID end setting value
1-100%(upper frequency limit reference)
0.1%
20
3201
PID control action selection
0
:
Open loop control
1
:
PID1 control
2
:
PID2 control
3
:
For factory adjustment
4
:
External terminal switching PID control
5
:
Timing switch PID control
1
0
3203
External PID control selection
0
:
No external PID control
1
:
PID1 external control
2
:
PID2 external control
3
:
For factory adjustment
4
:
PID1, PID2 external control
5
:
For factory adjustment
6
:
For factory adjustment
1
0
3204
External PID operation mode
selection
1
:
Operation interlocked with inverter operation
2
:
PID output after power input
3
:
PID output controlled by external terminals
1
1
3205
PID constitution selection
0
:
Without command value addition calculation
1
:
With command value addition calculation
1
0
3206
Command value addition calculation
PID control gain
0.01-100
0.01
1
3207
PID1/PID2 switching time
0.1-6000 minute(s)
0.1min.
0.1
【
PID Control Action Selection
】
F3201
PID control action selection
The function to select PID action.
● When setting F3201≠0, the following PID controls can be selected.
·F3201=0: Normal operation mode without PID control
·F3201=1: PID1 control mode
·F3201=2: PID2 control mode
·F3201=3: For factory adjustment
·F3201=4: PID control mode switched by external terminals
·F3201=5: PID control mode switched by timing
● PID control is effective in vector control of V/f and speed control mode.
● The basic formation of PID1 and PID2 are the same, therefore they can be used separately or combinedly.
● Details of each PID control mode is sorted according to the category of each function.
Note: During the operation status of inverter stopping, DC braking, excitation and so on, the PID control will not be used.