Description of Functions
System function
The inverter system, repair and maintenance functions as well as function blocks for operation setting of the control panel
are described as follows.
F1601
Copy function
This function transfers the function code data from the host side to the operation panel side or other hosts.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1601
Copy function
0
:
Inactive
1: Transfer the current code data to the
operation panel
2: Transfer the contents stored by operation
panel to the inverter host (excluding the
motor parameters measured)
3: Transfer the contents stored by operation
panel to the inverter host (including the
motor parameters measured)
1
0
●
Transfer the current function code data to the operation panel, and then to the host of copying side. When copying,
― ‖or a flashing ― ‖ will be displayed on 7-segment monitor.
●
To transfer data to the host of copying side, turn the power OFF before transmission in order to re-close the
inverter to reset.
●
When the motor parameters are set by F5001 - F5017, the copy function can not be used. Because during
replication, if the motor parameters conflicts with the set value of other function code(s), the motor parameters or
the conflicted function code(s) will be initialized. When motor parameters are set by F5009 - F5014, set F1601 = 3
to transfer data to the host.
(Sequence) Sequence for copying to other inverter(s).
1 Transfer the current function code data to the operation panel with F1601=1. Refer to the sequence of 5-5-1.
2 During transmission of data, the flashing ― ‖ is displayed. Please wait for the display of until it
disappears.
3 Turn the power OFF, remove the operation panel and install it to other host. Please also turn OFF the power of other
hosts before work.
4 Turn ON the power of other hosts.
5 Transfer data from the operation panel to other hosts with F1601 = 2.
6 During transmission of data, the flashing ― ‖ is displayed. Please wait for the display of until it
disappears.
7 After the transmission of data to the copy side and before operation, turn the power OFF to reset inverter.
●
As an exception, the active codes and data of F1320, F1601, F1602, F1604, all of F18XX blocks, all of F33XX
blocks, F5001 - F5008, F5015 - 5017, F6010 - F6016, F6117, F6118, as well as optional functions can not be
copied. And, in case of copy between different inverter capacities and rated voltages, the data may not be copied
depending on its contents. (e.g.: F1005)
●
The copy function can not be used during operation of the inverter. Please stop the inverter before copying.
Note 1:
Since copy function is subject to software version, data may not be copied due to compatibility of the
software version.
* For upgrade, please contact the sales shops.
Note 2: In the event of an error during data transmission to operation panel, please do not transfer data to the same or any
other inverter.