- 146 -
7-3
Description of Functions
Table 7-1 Multifunctional input codes
Function code
No.
Input terminal
name
Data range
Initial value
(symbol)
F1414
DI1
0-255
1 (FR)
F1415
DI2
2 (RR)
F1416
DI3
3 (2DF)
F1417
DI4
4 (3DF)
F1418
DI5
5 (MBS)
F1419
DI6
6 (ES)
F1420
DI7
7 (RST)
F1421
DI8
8 (AD2)
Table 7-2 Multifunctional input signals
Data No.
Symbol
Function
Data No.
Symbol
Function
0
—
Unused terminal
57
P0
Zero speed command
1
FR
Forward run command
58
Multiplexed terminal
FR+CCL
2
RR
Reverse run command
59
Multiplexed terminal
RR+CCL
3
2DF
Multi-speed command 1
64
Multiplexed terminal
FR+MBS
4
3DF
Multi-speed command 2
65
Multiplexed terminal
RR+MBS
5
MBS
Free run command
67
Multiplexed terminal
2DF+AD2
6
ES
External abnormal stop command
68
Multiplexed terminal
2DF+AD3
7
RST
Alarm reset command
69
Multiplexed terminal
3DF+AD2
8
AD2
2nd,
4th
acceleration/deceleration
command or up terminal
70
Multiplexed terminal
3DF+AD3
9
AD3
2nd,
4th
acceleration/deceleration
command or down terminal
71
A×10
Electric gear ×10 (option)
10
JOG
Jog operation command
72
A×100
Electric gear ×100 (option)
11
5DF
Multi-speed command 3
74
2MAX
2nd Upper frequency limit selection
*
1
12
9DF
Multi-speed command 4
75
3MAX
3rd Upper frequency limit selection
*
2
13
Multiplexed terminal
FR+JOG
76
VFPID
V/f-PID control switching terminal
14
Multiplexed terminal
RR+JOG
77
PIDLCK
PID control locking terminal
15
Multiplexed terminal
FR+AD2
79
DCBRK
DC braking command
16
Multiplexed terminal
RR+AD2
83
For factory
adjustment
17
Multiplexed terminal
FR+AD3
84
S2
2nd S-shaped acceleration / deceleration
time command
18
Multiplexed terminal
RR+AD3
85
PIDL
PID switching terminal (PIDL)
19
Multiplexed terminal
FR+2DF
86
PIDH
20
Multiplexed terminal
RR+2DF
87
RPID1
PID1 reset terminal
21
Multiplexed terminal
FR+3DF
88
PID1EX
PID1 External terminal selection
22
Multiplexed terminal
RR+3DF
89
PID2EX
PID2 External terminal selection
23
Multiplexed terminal
FR+2DF+3DF
91
IHOLD
PID integral value hold terminal
24
Multiplexed terminal
RR+2DF+3DF
92
ICLEAR
PID integral value clear terminal
25
Multiplexed terminal
FR+AD2+2DF
109
RCCL
Deviation counter reverse run clear
signal
26
Multiplexed terminal
RR+AD2+2DF
114
1DFA
1st speed frequency selection 1
27
Multiplexed terminal
FR+AD2+3DF
115
1DFB
1st speed frequency selection 2
28
Multiplexed terminal
RR+AD2+3DF
116
Multiplexed terminal
1DFA+1DFB
29
Multiplexed terminal
FR+AD2+2DF+3DF
117
ROPE
Control authorization selection 1
30
Multiplexed terminal
RR+AD2+2DF+3DF
118
RCOM
Control authorization selection 2
31
Multiplexed terminal
FR+AD3+2DF
119
Multiplexed terminal
ROPE+RCOM
32
Multiplexed terminal
RR+AD3+2DF
120
Multiplexed terminal
1DFA+ROPE
33
Multiplexed terminal
FR+AD3+3DF
121
Multiplexed terminal
1DFB+RCOM
34
Multiplexed terminal
RR+AD3+3DF
122
Multiplexed terminal
1DFA+1DFB+ROPE+RCOM
35
Multiplexed terminal
FR+AD3+2DF+3DF
123
VTC
Control switching of the speed - torque
36
Multiplexed terminal
RR+AD3+2DF+3DF
128
TREV
Inverted signal of the torque command
37
PTR multiplexed
terminal
Simple scheduled operation counter reset
signal
129
RREV
Inverted signal of the direction of
rotation
38
T-FCL
Keep or clear frequency
130
RUN
Run command (3wired operation)
39
Multiplexed terminal
FR+5DF
131
STOP
Stop command (3wired operation)
40
HD
Operation signal hold command
135
FR/RR
Signal of the direction of rotation
(3wired operation)
45
CP
Command pulse blocking signal (option)
136
R3W
Control authorization selection3
46
CCL
Deviation counter clear signal
137
Multiplexed terminal
ROPE+RCOM+R3W
47
PC
P control signal
253-255
For factory adjustment
*1
When the terminal is set to ON, F1316: limits the frequency with the 2nd upper frequency limit.
*2
When the terminal is set to ON, F1317: limits the frequency with the 3rd upper frequency limit.
Summary of Contents for SVCO6
Page 1: ...High Performance Vector Control Inverter Instruction Manual SANKEN ELECTRIC CO LTD ...
Page 2: ......
Page 324: ... 322 Memorandum ...
Page 325: ......