- 134 -
7-3
Description of Functions
F1202
State display selection
This function is used to select output data displayed on the 7-segment monitor on the operation panel in No-Units Display
mode.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1202
State display selection
1: No unit (multiple of F1203)
2: Output voltage [V]
3: DC voltage [V]
4: Active power [kW]
5: Apparent power [kVA]
6: Radiator temperature [
℃
]
7: Command speed [rpm]
8: PID1 feedback value [Hz]
9: PID2 feedback value [Hz]
10: VIF1 analog input value [Hz]
11: VIF2 analog input value [Hz]
12: VIF3 analog input value [Hz]
13: Output torque [%]
14: Partial excitation current [A]
15: Partial torque current [A]
16: Detecting position [mm]
29: Command frequency [Hz]
30: Command torque [%]
35: Detection speed [rpm](subPG)(option)
44: Reference frequency[Hz]
45: Output frequency[Hz]
50: DP control bit (option)
51: DP status bit (option)
52: Speed [rpm]
1
1
●
Output voltage: the output voltage of inverter.
●
DC voltage: the value of DC voltage applied to the inverter.
●
Active power: the actual power consumed on load.
●
Apparent power: the apparent power is used for displaying inverter output.
●
Radiator temperature: internal radiator temperature.
●
Command speed: the speed given by a command.
●
PID feedback value: the feedback value of PID control.
●
VIF analog input value: an analog signal value generated by voltage or current.
●
Command frequency: the frequency given by a command.
●
Reference frequency: the frequency is continuous driving frequency (target of output frequency).
●
Output frequency: the frequency is present driving frequency (the inverter output frequency).
●
Speed: the speed is reference speed during inverter stopping. The speed is command speed during inverter running.
The following display contents is shown only when the value of F1001 = 2, 3, 4, 5, 6.
●
Output torque: ratio of output torque to the rated torque.
●
Partial excitation current: the current value for providing motor excitation.
●
Partial torque current: the current value for providing motor torque.
●
Command torque: the torque given by a command.
The following display contents is shown only when the value of F1001 = 6.
●
Detecting position: the detecting position in position control.(Option)
* When three detecting positions are selected, even if the positioning is finished, " " will not be displayed.