- 173 -
-
173
-
C
h
ap
ter
7
7-3
Description of Functions
F1703
Output current limiting at constant speed
During constant-speed running, the action of output current limiting can be selected to be ON or OFF.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1703
Output current limiting at
constant speed
0: No function
1: with V/f (current acceleration /
deceleration time)
2: with V/f (1st acceleration / deceleration
time)
3: with V/f (2nd acceleration / deceleration
time)
4: with V/f (3rd acceleration / deceleration
time)
5: with V/f (4th acceleration / deceleration
time)
6: with V/f and speed control mode
(1st acceleration / deceleration time)
7: with V/f and speed control mode
(2nd acceleration / deceleration time)
8: with V/f and speed control mode
(3rd acceleration / deceleration time)
9: with V/f and speed control mode
(4th acceleration / deceleration time)
1
0
●
The motor control mode and acceleration / deceleration time can be selected separately. The acceleration /
deceleration time is the time set in F1012
-
F1021. (no external signal is required)
●
With the speed control mode (F1001=2 or 3), the output current can still be limited by the torque limiter even the
function of output current limiting at constant speed is OFF. Also, even if the function of output current limiting
at constant speed has been set (F1703=1
-
9), when the limit value on the torque limiter is low, the situation of
using a current limit lower than the values set in F1701 can still happen.
Note
1:
The code for limiting actions of output current at constant speed and the code for selecting of normal 1st - 4th
acceleration/deceleration time share the same code.
Note
2:
The situation that the output current is limited by speed control through the torque limiter may be used in case
that the values set in
F1012-F1021 don’t decelerate.
Note
3:
Use torque control mode, this function won’t work since the control methods are different.
Reference parameter
F1701 (output current limiting function)
F1012
-
F1015 (1st
-
4th acceleration time)
F1016
-
F1021 (1st
-
4th deceleration time)
Current limit
Output current
(F1701)
With output current
limiting at constant
speed(F1703≠0)
(
F
1
7
0
3
≠
0
)
F1703
Acceleration &
deceleration slopes
selected by
F1703
Time
Output frequency