7-3 Description of Functions
F1034
1st speed frequency selection A
F1035
1st speed frequency selection B
F1036
1st speed frequency selection C
Through configuring this function, the setting method of 1st speed frequency can be selected using the terminal block.
Code No.
Function Name
Data Content
Setting Resolution
Factory Presets
F1034
F1035
F1036
1st speed frequency
selection A
1st speed frequency
selection B
1st speed frequency
selection C
1: Operation panel
2: External analog VIF1 voltage (0-5V)
3: External analog VIF1 voltage (0-10V
or potentiometer)
4: External analog VIF2 voltage (0-5V)
5: External analog VIF2 voltage (0-10V
or potentiometer)
6: External analog VIF3 voltage (0-5V)
7: External analog VIF3 voltage (0-10V
or potentiometer)
8: External analog VIF1 current (4-20mA)
9: External analog VIF2 current (4-20mA)
10: External analog VIF3 current (4-20mA)
21: Terminal block stepping
22: Communication
25: Pulse train input
26: External analog VIF1 forward / reverse
run operation (0 - 10V, 5V reference)
27: External analog VIF2 forward / reverse
run operation (0 - 10V, 5V reference)
28: External analog VIF3 forward / reverse
run operation (0 - 10V, 5V reference)
29: Pulse train input (subPG
:
option)
1
1
1
1
●This function is a function for switching the setting methods of 1st speed frequency by use of 1DFA and 1DFB
terminals. Depending on the status of 1DFA and 1DFB terminals, the setting methods of 1st speed frequency can be
changed as the table below.
1DFA
1DFB
1st speed frequency action
OFF
OFF
Determine the 1st speed frequency according to the method selected by F1002
ON
OFF
Determine the 1st speed frequency according to the method selected by F1034
OFF
ON
Determine the 1st speed frequency according to the method selected by F1035
ON
ON
Determine the 1st speed frequency according to the method selected by F1036
●See items of F1002 for input modes.
●Even if 1DFA and 1DFB are ON, the frequency setting value in multi-segment speed (2nd - 16th speed) operation or
JOG operation is still the value set by F1021 or F2102
-
F2116.
●The same VIF input can be specified by F1002, F1034, F1035, and F1036.
●When any one code of F1034 - F1036 is set to VIF current input, the input resistance of VIF terminal changes as the
switching of 1DFA and 1DFB. Please note this when using VIF current input.