- 114 -
7-3
Description of Functions
F1011
Reference frequency for
acceleration/deceleration
F1012
1st acceleration time
F1013
2nd acceleration time
F1014
3rd acceleration time
F1015
4th acceleration time
F1016
1st deceleration time
F1017
2nd deceleration time
F1018
3rd deceleration time
F1019
4th deceleration time
F1020
JOG acceleration/deceleration time
Four different acceleration slops and deceleration slops can be independently set according to four different acceleration
times and deceleration times. And, F1020 is the function for setting acceleration and deceleration slopes in jog operation.
Code No.
Function Name
Data Content
Setting Resolution
Factory Presets
F1011
Reference frequency for
acceleration/deceleration
1-120Hz
0.01 Hz
※
F1012
1st acceleration time
0 -6,500 sec.
0.1 s
※
F1013
2nd acceleration time
0 -6,500 sec.
0.1 s
F1014
3rd acceleration time
0 -6,500 sec.
0.1 s
F1015
4th acceleration time
0 -6,500 sec.
0.1 s
F1016
1st deceleration time
0 -6,500 sec.
0.1 s
※
F1017
2nd deceleration time
0 -6,500 sec.
0.1 s
F1018
3rd deceleration time
0 -6,500 sec.
0.1 s
F1019
4th deceleration time
0 -6,500 sec.
0.1 s
F1020
JOG acceleration/deceleration time
0 -20 sec.
0.1 s
0.1 s
※
The representative parameters that are suitable for various models have been input.
Example) When F1011 = 50 Hz, F1012 = 5 seconds, the acceleration slope is set to 10Hz / s.
●
In the V/f mode, even if the acceleration/deceleration time is set to 0 s, the actual value will still be 0.1 s.
●
The 2nd thru 4th acceleration/deceleration times are selected by the combination of signals input to control input
terminals AD2 and AD3.