
- 288 -
7-4
Serial Communication Function
⑭
Processing of inverter communication error
·
The following error processing will be carried out when an error is detected in the message received from the
computer. According to error content, it can be divided into error response not sent and error response sent.
1
)
Error response not sent
·
Serial communication error
In case of parity error and other errors in serial communication
·
Error of received data frame length
When received data length is longer than maximum data length of 256-byte or shorter than the minimum
data length (address 1-byte + command code 1-byte + CRC 2-byte) of 4-byte
·
CRC Error
Error during receiving CRC checksum of data frame
·
Broadcast mode
In broadcast mode, no response is returned.
2
)
Error response sent
·
Command code not defined
When a command code is except 03H, 06H or 10H,
error detection will be carried out and an error code
will be returned.
·
PDU Error
When number of data for communication message has an error, an error code will be returned.
·
Address error
When starting address or starting a number of registers is beyond the following range of valid
address, an error code will be returned.
(at F4103=0: the time of register number A)
Reading command 2000
-
2019
Writing command 1000
-
1002
(at F4103=1: the time of register number B)
Reading command 9600
-
9619
Writing command 9500
-
9502
·
Error of specified execution
When setting the register with a value beyond the setting values listed in the data sheet (for frequency
setting of register number [1000
at F4103=0: the time of register number A,
9500
at F4103=1: the time of
register number B], the range of 0-60000 is valid), or no control is permitted when setting the start
command for register number [1001
at F4103=0: the time of register number A,
9501
at F4103=1: the
time of register number B], an error code will be returned.
⑮
List of error codes during function code setting
Error code
Description
01H
Command code not defined
02H
Address error
03H
PDU error
04H
Specified execution error
F0H
Inconsistency between function code number XXXX and setting value
F1H
Function code value setting too large, undefined user initialization, or an un-registered inverter number
F2H
Inconsistency between function code setting value and optional board
F3H
Inconsistency between function code setting value and option
F4H
Inverter operation, function code cannot be changed
F5H
Operation locked, function code cannot be changed
F9H
Function code cannot be changed in LV
FAH
Frequency setting is not allowed, please enter F1002 setting value
FBH
Inverter busy, please send message again
FCH
System reserved
FEH
Selection of undefined code (access the code with serial communication function)
Summary of Contents for SVCO6
Page 1: ...High Performance Vector Control Inverter Instruction Manual SANKEN ELECTRIC CO LTD ...
Page 2: ......
Page 324: ... 322 Memorandum ...
Page 325: ......