- 139 -
C
h
ap
ter
7
7-3
Description of Functions
F1316
2nd Upper frequency limit
F1317
3rd Upper frequency limit
A function for setting the upper limit of output frequency. If 2MAX is set to ON using multifunctional input terminals
(F1414 - F1421), then the 2nd Upper frequency limit will be used to limit frequency, if 3MAX is set to ON, then 3rd
Upper frequency limit will be used. If both of them are set to ON, then the upper frequency limit of F1007 will be used
for limiting frequency.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1316
2nd Upper frequency limit
5- 599Hz
0.01Hz
60
F1317
3rd Upper frequency limit
5- 599Hz
0.01Hz
60
F1318
Cooling fan ON/OFF control
This function is used to select the action of cooling fan for cooling inverter.
Code No.
Function Name
Data Content
Setting
Resolution
Factory Presets
F1318
Cooling fan ON/OFF
control
0: ON/OFF control
1: Normally ON
1
0
●
When ON/OFF control is selected, fan ON/OFF control will be automatically executed according to the radiator
temperature.
Note: In power-on test after the fan has been replaced, check that the fan is set to normally ON.