- 284 -
7-4
Serial Communication Function
■
Reading register address (at F4103=0: the time of register number A)
Processing
method
Register No.
Description
DEC
HEX
Reading
2000
7D0H
Alarm content
0 = No alarm; Other = list of alarm codes
※
1
2001
7D1H
Reading of command frequency
2002
7D2H
Reading of output frequency
2003
7D3H
Reading of output current
2004
7D4H
Reading of DC voltage
2005
7D5H
Reading of radiator temperature
2006
7D6H
Reading of load factor
2007
7D7H
Reading of Operation Status 1
BIT0-BIT4
JOG
+
16th speed operation (operation status)
0000
:
speed segment 0, JOG operation
00001
:
1st speed operation
00010
:
2nd speed operation
…..…..…..…..…..
10000
:
16th speed operation
BIT5
Operation by external analog input frequency
(operation status)
BIT6
Operation by option input frequency
(operation status)
BIT7
1 = warning; 0 = no warning
BIT8
1 = alarm; 0 = no alarm
BIT9 and above
System reserved
2008-2009
7D8H-7D9H
Reading of Operation Status 2
BIT0-BIT13
STATUS FLAG(32bit)
※
2
BIT14 and above
System reserved
2010
7DAH
Reading of Operation Status 3
System reserved
2011
7DBH
Reading of Operation Status 4
System reserved
2012
7DCH
Reading of external terminal input status 1
BIT0-BIT7
DI1-DI8 (ON/OFF)
1=ON; 0=OFF
BIT8 and above
System reserved
2013
7DDH
Reading of external terminal input status 1
BIT0-BIT2
DO1-DO3 (HIGH/LOW)
1=LOW; 0=HIGH
BIT3
RY1 (HIGH/LOW)
1=HIGH; 0=LOW
BIT4 and above
System reserved
2014
7DEH
Reading of output voltage
2015
7DFH
Reading of VIF1 control terminal input value
2016
7E0H
Reading of VIF2 control terminal input value
2017
7E1H
Reading of VIF3 control terminal input value
2018
7E2H
Reading of AOUT1 output value
2019
7E3H
Reading of AOUT2 output value
2020
7E4H
Reading of frequency
2021
7E5H
Reading of speed
2022
7E6H
Reading of active power
2023
7E7H
Reading of apparent power
2024
7E8H
Reading of command speed
2025
7E9H
Reading of PID1 feedback value
2026
7EAH
Reading of PID2 feedback value
2027
7EBH
Reading of output torque
2028
7ECH
Reading of excitation current
2029
7EDH
Reading of torque current
2030
7EEH
Reading of detecting position
2031
7EFH
Reading of command torque
2032
7F0H
Reading of speed (sub PG) (option)
2033
7F1H
Reading of target frequency
2034-2999
7F2H-BB7H
System reserved
※
1
Please refer to list of alarm codes for communication with dedicated protocol.
※
2
STATUSFLAG(status flag)
Summary of Contents for SVCO6