7-3
Description of Functions
Code No.
Function Name
Date Content
Setting
Resolution
Factory
Presets
3018
PID1 control feedback value
(communication function)
0-6000
0.1
0
3019
Frequency corresponding to
PID1 control maximum
command value
0-600Hz
0.01Hz
60
3101
PID2 command value input
switching
1
:
Frequency
2
:
External analog VIF1 voltage (0-5V)
3
:
External analog VIF1 voltage (0-10V or potentiometer)
4
:
External analog VIF2 voltage (0-5V)
5
:
External analog VIF2 voltage (0-10V or potentiometer
)
6
:
External analog VIF3 voltage (0-5V)
7
:
External analog VIF3 voltage (0-10V or potentiometer)
8
:
External analog VIF1 current (4-20mA)
9
:
External analog VIF2 current (4-20mA)
10
:
External analog VIF3 current (4-20mA)
11
:
Function code setting (by F3017)
98: Pulse train input subPG(option)
99
:
Pulse train input
1
1
3102
PID2 feedback input switching 0
:
No input
1
:
External analog VIF1 voltage (0-5V)
2
:
External analog VIF1 voltage (0-10V or potentiometer)
3
:
External analog VIF2 voltage (0-5V)
4
:
External analog VIF2 voltage (0-10V or potentiometer)
5
:
External analog VIF3 voltage (0-5V)
6
:
External analog VIF3 voltage (0-10V or potentiometer)
7
:
External analog VIF1 current (4-20mA)
8
:
External analog VIF2 current (4-20mA)
9
:
External analog VIF3 current (4-20mA)
10
:
Communication mode
98: subPG feedback PID (option)
99
:
PG feedback PID
1
0
3103
PID2 control proportional gain 0-100
0.01
0.1
3104
PID2 control integral time
0.01-100 second(s)
0.01s
0.1
3105
PID2
control differential time
0-100 second(s)
0.01s
0
3106
PID2 control integral
separation judgment value
5-100%(upper frequency limit reference)
0.1%
100
3107
PID2 feedback signal input
filter time constant
1-500(set value 1=10ms)
1
10
3108
Indirect PID2 input reference
5-100%(target value reference)
0.1%
20
3109
PID2 deviation limit value
0
:
No limit
1-100%(upper frequency limit reference)
0.1%
100
3110
PID2 output limit value
0
:
No limit
1-100%(upper frequency limit reference)
0.1%
100
3111
PID2 operation polarity
switching
1
:
command value - feedback value
2
:
feedback value - command value
1
1
3112
PID2 gain polarity switching
1
:
The positive or negative deviation indicates the same gain
2
:
The positive or negative deviation indicates different gains
1
1
3113
PID2 command value gain
0-50
0.01
1
3114
PID2 feedback value gain
0-50
0.01
1
3115
PID2 control proportional gain
(negative
:
F3012=2)
0-100
0.01
0.1
3116
PID2 control integral time
(negative
:
F3012=2)
0.01-100 second(s)
0.01s
0.1
3117
PID2 control command value
0-6000
0.1
0
3118
PID2 control feedback value
(communication function)
0-6000
0.1
0
Summary of Contents for SVCO6
Page 1: ...High Performance Vector Control Inverter Instruction Manual SANKEN ELECTRIC CO LTD ...
Page 2: ......
Page 324: ... 322 Memorandum ...