3.1.3. Terminal block connector (Detachment Method)
<Removing>
<Attaching>
※
The example figure shows the TN model.
Terminal block connector
〈Figure of LAN unit from the underside〉
Raise the lever
Referring to the drawing, depress the lever
on the right and left of the terminal block
connector to unlock it, and pull the terminal
block connector straight out.
Push the terminal block connector into the LAN unit until the levers
can be locked in place.
(When pushing the terminal block connector in place, the lever will
temporarily move up, before it moves down and locks into place.)
3.2. Wiring
3.2.1. Terminal Block Connector Pin Arrangement
■
Recommended lead wire specifications
UL1007/UL1430
Wire Type
0.2-1.5mm
2
Wire Gauge (Solid Wire)
AWG24-16
Wire Gauge (Frayed Wire)
7
8
9
10
11
12
1
2
3
4
5
6
Temperature rating should be above 75
o
C, and
the conductor material should be of copper wire.
COM
Flashing/Pulse Enable
Common
Mode Change
Input 7
Input 5
Power Wire
(Signal Wire Side)
Power Wire
Input 4
Input 3
Input 2
Input 1
Input 6
3.2.2. Wiring the Terminal Block
Slot
2
1
3
❶
A
minus driver etc. is placed on the slot and pushed into
the slot of the terminal block connector. (at a slight angle)
❷
T
he stripped side of the lead wire is inserted in the slot.
❸
T
he driver is then extracted from the slot. (Check to make
sure the lead wire has been locked in place.)
Point
The minus driver blade should be no less than 2.5mm in width and 0.4mm in
thickness. Any object that fits the dimensions is also ok.
Do not forcibly push the slot more than necessary with the driver. Failure to comply
may damage the unit.
Strip 6-7mm of wire insulation from the wire before inserting it in the Terminal Block.
When removing the lead wire, Do not just pull to remove.
(Be sure to slide the minus driver etc. into the slot to unlock it.)