51
Signal Tower LA6-POE Operation Manual
5.4. Mirroring
Up
to nine
LA6-POE Signal Towers can be in the same status by sending the status of the LA6-POE which is being
controlled by the Master via the signal line, to another
one of eight
LA6-POE Signal Towers connected within the network.
・・・
Mirroring original signal
line control method
Mirroring information update
Mirroring destination
command control method
(Maximum: 8 LA6-PoE)
on Status Change
When setting the LA6-POE control by a signal line, (Refer to “4.9.1 Setting up the Mirroring Source” on page 29)
When setting the LA6-POE control by command, (Refer to “4.9.2 Setup Mirroring Destination Point” on page 30)
MEMO
• The maximum possible number of mirrored LA6-POE Signal Towers is eight units.
• Even if the mirroring source status does not change, the mirroring information is updated
every 10 seconds.
• Even if a clear is executed at the mirroring destination, if 10 seconds elapse, or the signal line
status changes, the mirroring source status will be reflected.