Signal Tower LA6-POE Operation Manual
5.1.5. Managing Detailed Command Control
Command Description
In the data area, the color and behavior pattern of each LED unit tier and buzzer pattern (1 to 11) can be controlled
when being specified.
Transmission Data Format
Product Category
AB
Identifier
D
Open
Data Size
Data Area 7 bytes
41H
42H
44H
00H
00H
07H
See Below
Product Category
The product is classified in “AB.”
Identifiers
“D” is used.
Data Area
Data Area 7 bytes
LED Unit
Flashing
Operation Buzzer
1
2
3
4
5
6
7
Tier 1
Color
Tier 2
Color
Tier 3
Color
Tier 4
Color
Tier 5
Color
Flashing
Operation
Patterns
1-11
LED Unit
Flashing Operation
Buzzer
00H: Off
00H: Flashing OFF
00H: Stop
01H: Red
01H: Flashing ON
01H: Pattern 1
02H: Amber
02H: Pattern 2
03H: Lemon
03H:
Pattern 3
04H: Green
04H:
Pattern 4
05H: Sky Blue
05H:
Pattern 5
06H: Blue
06H:
Pattern 6
07H: Purple
07H:
Pattern 7
08H: Pink
08H:
Pattern 8
09H: White
09H:
Pattern 9
0AH: Pattern10
0BH:
Pattern 11
Reply Data
Normal Response (1 byte)
Abnormal Response (1 byte)
ACK
NAK
06H
15H
Command Transmission Example
1st Tier : Green, 2nd Tier: Blue, 3rd Tier: Off, 4thTier: White, 5th Tier: Red, Flashing: Off, Buzzer: Pattern 11
Product Category
AB
Identifier
D
Open
Data Size
Data Area
41H
42H
44H
00H
00H
07H
04H
06H
00H
09H
01H
00H
0BH
MEMO
• The color set in the signal Tower mode becomes invalid.
• When the flashing operation is turned ON, all tiers will flash.