21
Signal Tower LA6-POE Operation Manual
[Data writing method in "EDITOR for LA series"]
①
The product changes to standby status (all signal inputs OFF).
(Power supply input can be ON or OFF, whichever is easier)
②
Open the USB cover to the product, use the MicroUSB cable to connect the product to the personal computer.
Personal
Computer
LA6 (back)
Micro-USB cable
(
Not included with this product.
)
USB Cover
Micro-USB Connector
(Micro-B Female)
③
Click the "Send" button for the “EDITOR for LA series”.
④
From the start of data transfer, it takes about 15 seconds before the "Transfer was completed" prompt is
displayed.
⑤
Remove the micro-USB cable and close the USB cover completely.
!
WARNING
■
When transferring data via USB connection, do not allow the supply voltage from this product to contact with the
personal computer, or it's peripheral devices. Failure to comply will result in product damage due to combustion or
fire.
As an example, if the positive power terminal is connected to ground and the personal computer FG (housing), which
in turn, makes a connection with this product via the USB connection, it should not be grounded because of the
reverse polarity.
There are some personal computers which have the USB port connector and negative terminal of the personal
computer in contact with the FG (housing).
Personal computers with such USB connections made, should have the FG (housing) of the personal computer and
the negative terminal of the USB port of the product connected.
If the case is where the personal computer has the metal chassis as the positive grounding of the supplied power
source to the product, the product will have a 24V potential applied to the negative terminal of the USB port of the
product, thus will damage product by burning-up.
!
NOTICE