Signal Tower LA6-POE Operation Manual
Coil/Register Numbers Register Address Control Allocation
Example Data Integer
40001
1 (01H)
1st LED Unit Tier
Does Control, Steady on: 0101H = 257
Does Control, Flashing: 0102H = 258
40002
2 (02H)
2nd LED Unit Tier
Does Control, Steady on: 0101H = 257
Does Control, Flashing: 0102H = 258
40003
3 (03H)
3rd LED Unit Tier
Does Control, Steady on: 0101H = 257
Does Control, Flashing: 0102H = 258
40004
4 (04H)
4th LED Unit Tier
Does Control, Steady on: 0101H = 257
Does Control, Flashing: 0102H = 258
40005
5 (05H)
5th LED Unit Tier
Does Control, Steady on: 0101H = 257
Does Control, Flashing: 0102H = 258
40006
6 (06H)
Buzzer
Does Control, buzzer pattern 1 on: 0101H = 257
Does Control, buzzer pattern 2 on: 0102H = 258
40007
7 (07H)
Smart Mode
Does Control, Group Number 1: 0101H = 257
Does Control, Group Number 15: 010FH = 271
40008
8 (08H)
Clear
Execute Clear: 0001H = 1
40009
9 (09H)
Mute
Mute cancel: 0000H = 0
Mute execution: 0001H = 1
40010
10 (0AH)
STOP
STOP cancel: 0000H = 0
STOP execution: 0001H = 1
40011
11 (0BH)
Pulse Trigger Input
Pattern change: 0001H = 1
5.3.5. Command Transmission Example
<Read Input Status (02H)>
Control Command
Transaction
Identifier
Protocol
Identifier
Field
Length
Unit
Identifier
Function
Code
Data
Start Address
Number of
inputs
00H 00H
00H 00H
00H 06H
01H
02H
00H 00H
00H 08H
Specify -1 as the first input address to obtain the status for the start address.
For the number of inputs, specify the number of inputs to get a status from.
Reply Command
In this example, contact input 2 is set to ON and all other contact inputs are OFF.
Transaction
Identifier
Protocol
Identifier
Field
Length
Unit
Identifier
Function
Code
Data
byte Count
Input 1-8
00H 00H
00H 00H
00H 04H
01H
02H
01H
02H
Input (8 Bits)
8 7 6 5 4 3 2 1
Status (02H)
0 0 0 0 0 0 1 0