5.1.9. Detailed Status Acquisition Command
Command Description
The following information can be acquired.
・
The status of the signal line/contact input.
・
The LED unit status.
・
The LED unit color information.
・
The MAC address of this product.
Transmission Data Format
Product Category
AB
Identifier
E
Open
Data Size
41H
42H
45H
00H
00H
00H
Product Category
The product is classified in “AB.”
Identifiers
“E” is used.
Data Area
There is no data area.
Reply Data
[ Normal Response (40 bytes): When running in Signal Tower Mode ]
1 byte 2 bytes 3 bytes 4 bytes 5 bytes 6 bytes 7 bytes 8 bytes 9 bytes 10 bytes 11 bytes 12 bytes 13 bytes 14 bytes
MAC address
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8
The MAC address of this product is stored.
00H: OFF
01H: ON
15 bytes
16 bytes 17 bytes 18 bytes 19 bytes 20 bytes
21 bytes
22 bytes
23 bytes
Mode
Open
1st Tier of LED unit
Status
R
G
B
00H
(Signal Tower mode)
00H
00H
00H
00H
00H: Off
01H: On
02H: Flashing
00H-FFH
00H-FFH
00H-FFH
24 bytes
25 bytes 26 bytes 27 bytes 28 bytes
29 bytes 30 bytes 31 bytes
2nd Tier of LED unit
3rd Tier of LED unit
Status
R
G
B
Status
R
G
B
00H: Off
01H: On
02H: Flashing
00H-FFH 00H-FFH 00H-FFH 00H: Off
01H: On
02H: Flashing
00H-FFH 00H-FFH 00H-FFH
32 bytes
33 bytes 34 bytes 35 bytes 36 bytes
37 bytes 38 bytes 39 bytes 40 bytes
4th Tier of LED unit
5th Tier of LED unit
Buzzer
Status
R
G
B
Status
R
G
B
Status
00H: Off
01H: On
02H: Flashing
00H-FFH 00H-FFH 00H-FFH 00H: Off
01H: On
02H: Flashing
00H-FFH 00H-FFH 00H-FFH 00H: Stop
01H: Buzzer Pattern 1
02H: Buzzer Pattern 2
03H: Buzzer Pattern 3/
buzzer sounds when
the buzzer inputs are
simultaneously entered
(Cont)
0AH: Buzzer pattern 10
0BH: Buzzer pattern 11
MEMO
• The color information of the LED unit is stored in the RGB color model.
Refer to " Correspondance tabele of RGB color model" on page 93