F-13
Technical Specifications
AC30V series Variable Speed Drive
SUPPLY SHORT CIRCUIT RATING
The following drives when fitted with UL Listed fuses are suitable for use on a circuit capable of delivering not more than:
Frames D, E, F, G: 5,000 RMS Symmetrical Amperes, 480V maximum
Frame H & J: 10,000 RMS Symmetrical Amperes, 480V maximum
Frame K: 18,000 RMS Symmetrical Amperes, 480V maximum
Refer to Appendix C: “Compliance” – Solid –State Short Circuit Protection
When group installed with the specified line reactor frame D, E, F, G, H, J & K sizes may be used on a supply rating delivering not more than
50,000 RMS Symmetrical amperes, 480V maximum, see table below for further information:
Frame Size
Motor Power
Parker Part Number
MTE Part Number
Inductance mH
Rated amps
D
1.1kW / 1.5hp
CO470651
RL-00402
6.5
4
D
1.5kW / 2hp
CO470651
RL-00402
6.5
4
D
2.2kW / 3hp
CO352782
RL-00803
5
8
D
3kW
CO352782
RL-00803
5
8
D
4kW / 5hp
CO470652
RL-00802
3
8
D
5.5kW / 7.5hp
CO352783
RL-01202
2.5
12
E
7.5kW / 10hp
CO352785
RL-01802
1.5
18
E
11kW / 15hp
CO352786
RL-02502
1.2
25
F
15kW / 20hp
CO352901
RL-03502
0.8
35
F
18kW / 25hp
CO352901
RL-03502
0.8
35
G
22kW / 30hp
CO352902
RL-04502
0.7
45
G
30kW / 40hp
CO352903
RL-05502
0.5
55
G
37kW / 50hp
CO352904
RL-08002
0.4
80
H
45kW / 60hp
CO352904
RL-08002
0.4
80
H
55kW / 75hp
CO352905
RL10002
0.3
100
H
75kW / 100hp
CO352906
RL13002
0.2
130
J
90kW / 125hp
CO470057
RL-16002
0.15
160
J
110kW / 150hp
CO470046
RL-20002
0.11
200
J
132kW / 200hp
CO470046
RL-25002
0.09
250
K
160kW / 250hp
CO470047
RL-32002
0.075
320
K
200kW / 300hp
CO470048
RL-40002
0.06
400
K
250kW / 350hp
CO470049
RL5-50002
0.05
500
380-480V