Parameter Reference
AC30V series Variable Speed Drive
Ramp
Parameters::Motor Control::Ramp
This function forms part of the reference generation. It provides the facility to control the rate at which the Drive will respond to a changing
setpoint demand.
PNO Parameter Descriptions
Seq Stop Method VHz
Volts/Hz control mode only
Selects stopping mode that the controller will use once the run command has been removed. The choices are:
Enumerated Value : Stopping Mode
0 : DISABLED VOLTAGE, (COAST)
1 : RAMP
2 : STOP RAMP
3 : DC INJECTION
When DISABLED VOLTAGE ( COAST ) is selected the motor will free-wheel. When RAMP is selected the Drive will decelerate using
the reference ramp deceleration time, provided it is non-zero. When STOP RAMP is selected the motor will decelerate in
Stop Ramp
Time
. When DC INJECTION is selected the motor is stopped by applying dc current.
Seq Stop Method SVC
All Control modes except Volts/Hz
Selects stopping mode that the controller will use once the run command has been removed. The choices are:
Enumerated Value : Stopping Mode
0 : DISABLED VOLTAGE, (COAST)
1 : RAMP
2 : STOP RAMP
When DISABLED VOLTAGE ( COAST ) is selected the motor will free-wheel. When RAMP is selected the Drive will decelerate using
the reference ramp deceleration time, provided it is non-zero. When STOP RAMP is selected the motor will decelerate in
Stop Ramp
Time
.
Ramp Type
Select the ramp type:
Enumerated Value : Ramp Type
0 : LINEAR
1 : S Ramp