Parameter Reference
D-138
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units WQ
View
Notes MBus
0696 First Trip
Monitor::Trips
Parameters::Trips::Trips Status
USINT
(enum)
0:NONE
1:01 OVER VOLTAGE
2:02 UNDER VOLTAGE
3:03 OVER CURRENT
4:04 STACK FAULT
5:05 STACK OVER CURRENT
6:06 CURRENT LIMIT
7:07 MOTOR STALL
8:08 INVERSE TIME
9:09 MOTOR I2T
10:10 LOW SPEED I
11:11 HEATSINK OVERTEMP
12:12 INTERNAL OVERTEMP
13:13 MOTOR OVERTEMP
14:14 EXTERNAL TRIP
15:15 BRAKE SHORT CCT
16:16 BRAKE RESISTOR
17:17 BRAKE SWITCH
18:18 LOCAL CONTROL
19:19 COMMS BREAK
20:20 LINE CONTACTOR
21:21 PHASE FAIL
22:22 VDC RIPPLE
23:23 BASE MODBUS BREAK
24:24 24 V OVERLOAD
25:25 PMAC SPEED ERROR
26:26 OVERSPEED
27:27 STO ACTIVE
28:28 FEEDBACK MISSING
29:29 INTERNAL FAN FAIL
30:30 CURRENT SENSOR
31:31 POWER LOSS STOP
NEVER
OPERATOR
01919
0697 Enable 1 - 32
Parameters::Trips::Trips Status
DWORD
(bitfield)
0000FF7F
5:06 CURRENT LIMIT
6:07 MOTOR STALL
7:08 INVERSE TIME
8:09 MOTOR I2T
9:10 LOW SPEED I
11:12 INTERNAL OVERTEMP
12:13 MOTOR OVERTEMP
13:14 EXTERNAL TRIP
14:15 BRAKE SHORT CCT
15:16 BRAKE RESISTOR
16:17 BRAKE SWITCH
17:18 LOCAL CONTROL
18:19 COMMS BREAK
19:20 LINE CONTACTOR
20:21 PHASE FAIL
21:22 VDC RIPPLE
22:23 BASE MODBUS BREAK
23:24 24 V OVERLOAD
24:25 PMAC SPEED ERROR
25:26 OVERSPEED
28:29 INTERNAL FAN FAIL
29:30 CURRENT SENSOR
30:31 POWER LOSS STOP
ALWAYS
TECHNICIAN
01921
0703 Enable 1 - 32.06 CURRENT LIMIT
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01933
0704 Enable 1 - 32.07 MOTOR STALL
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01935
0705 Enable 1 - 32.08 INVERSE TIME
Parameters::Trips::Trips Status
BOOL
FALSE
ALWAYS
TECHNICIAN
01937
0706 Enable 1 - 32.09 MOTOR I2T
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01939
0707 Enable 1 - 32.10 LOW SPEED I
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01941
0709 Enable 1 - 32.12 INTERNAL OVERTEMP
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01945
0710 Enable 1 - 32.13 MOTOR OVERTEMP
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01947
0711 Enable 1 - 32.14 EXTERNAL TRIP
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01949
0712 Enable 1 - 32.15 BRAKE SHORT CCT
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01951
0713 Enable 1 - 32.16 BRAKE RESISTOR
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01953
0714 Enable 1 - 32.17 BRAKE SWITCH
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01955
0715 Enable 1 - 32.18 LOCAL CONTROL
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01957
0716 Enable 1 - 32.19 COMMS BREAK
Parameters::Trips::Trips Status
BOOL
TRUE
ALWAYS
TECHNICIAN
01959