D-133
Parameter Reference
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units WQ
View
Notes MBus
0362 Slew Rate Decel Limit
Parameters::Motor Control::Slew Rate
REAL
500
1 to 1200
Hz/s ALWAYS
TECHNICIAN
01251
0364 Stabilisation Enable
Parameters::Motor Control::Stabilisation
BOOL
TRUE
ALWAYS
TECHNICIAN
01255
0371 Terminal Voltage Mode
Parameters::Motor Control::Voltage Control
USINT
(enum)
0
0:NONE
1:FIXED
2:AUTOMATIC
ALWAYS
TECHNICIAN
01269
0374 Motor Base Volts
Parameters::Motor Control::Voltage Control
REAL
100.00
0.00 to 115.47
%
ALWAYS
TECHNICIAN
01275
0380 Power kW
Monitor::Energy Meter
Parameters::Motor Control::Energy Meter
REAL
x.xx
0.00 to 1000000.00
kW
NEVER
TECHNICIAN
01287
0381 Power HP
Same as PNO 380
REAL
x.xx
0.00 to 1000000.00
HP
NEVER
TECHNICIAN
01289
0382 Reactive Power
Same as PNO 380
REAL
x.xx
0.00 to 1000000.00
kVAr NEVER
TECHNICIAN
01291
0383 Energy kWh
Same as PNO 380
REAL
x.xx
0.00 to 10000000.00
kWh NEVER
TECHNICIAN
1
01293
0385 Power Factor Est
Same as PNO 380
REAL
x.xx
0.00 to 1.00
NEVER
TECHNICIAN
01297
0386 Power Factor Angle Est
Parameters::Motor Control::Energy Meter
REAL
x.xx
0.00 to 90.00
deg
NEVER
TECHNICIAN
01299
0389 Reset Energy Meter
Parameters::Motor Control::Energy Meter
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01305
0390 Duty Selection
Setup::Motor Control::Control and Type
Parameters::Motor Control::Feedbacks
USINT
(enum)
1
0:HEAVY DUTY
1:NORMAL DUTY
STOPPED
TECHNICIAN
01307
0392 DC Link Voltage
Monitor::Motor and Drive
Parameters::Motor Control::Feedbacks
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01311
0393 Actual Speed RPM
Same as PNO 392
REAL
x.xx
-100000.00 to 100000.00
RPM NEVER
TECHNICIAN
01313
0394 Actual Speed rps
Same as PNO 392
REAL
x.xx
-1500.00 to 1500.00
rev/s NEVER
TECHNICIAN
01315
0395 Actual Speed Percent
Same as PNO 392
REAL
x.xx
-200.00 to 200.00
%
NEVER
OPERATOR
01317
0396 DC Link Volt Filtered
Same as PNO 392
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01319
0397 id
Parameters::Motor Control::Feedbacks
REAL
x.x
-500.0 to 500.0
%
NEVER
ENGINEER
01321
0398 iq
Parameters::Motor Control::Feedbacks
REAL
x.x
-500.0 to 500.0
%
NEVER
ENGINEER
01323
0399 Actual Torque
Same as PNO 392
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01325
0400 Actual Field Current
Same as PNO 392
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01327
0401 Motor Current Percent
Same as PNO 392
REAL
x.x
0.0 to 500.0
%
NEVER
TECHNICIAN
01329
0402 Motor Current
Same as PNO 392
REAL
x.x
0.0 to 2000.0
A
NEVER
TECHNICIAN
01331
0403 100% Stack Current A
Parameters::Motor Control::Feedbacks
REAL
x.x
0.0 to 500.0
A
NEVER
TECHNICIAN
01333
0404 Stack Current (%)
Parameters::Motor Control::Feedbacks
REAL
x.
0 to 500
%
NEVER
TECHNICIAN
01335
0405 Motor Terminal Volts
Same as PNO 392
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01337
0406 CM Temperature
Same as PNO 392
REAL
x.x
-25.0 to 200.0
°C
NEVER
ENGINEER
01339
0407 Heatsink Temperature
Same as PNO 392
REAL
x.x
-25.0 to 200.0
°C
NEVER
ENGINEER
01341
0408 Elec Rotor Speed
Parameters::Motor Control::Feedbacks
REAL
x.x
-1500.0 to 1500.0
Hz
NEVER
OPERATOR
01343
0409 Heatsink OT Trip
Parameters::Motor Control::Feedbacks
REAL
x.x
0.0 to 200.0
°C
NEVER
OPERATOR
01345
0410 Heatsink OT Warning
Parameters::Motor Control::Feedbacks
REAL
x.x
0.0 to 200.0
°C
NEVER
OPERATOR
01347
0411 Heatsink Hot Warning
Parameters::Motor Control::Feedbacks
REAL
x.x
0.0 to 200.0
°C
NEVER
OPERATOR
01349
0412 Stack Frequency
Parameters::Motor Control::Pattern Generator
REAL
4.00
2.00 to 16.00
kHz
ALWAYS
ENGINEER
6
01351
0413 Random Pattern IM
Parameters::Motor Control::Pattern Generator
BOOL
TRUE
ALWAYS
ENGINEER
01353
0414 Deflux Delay
Parameters::Motor Control::Pattern Generator
TIME
1.000
0.000 to 10.000
s
STOPPED
ENGINEER
6
01355
0415 Positive Torque Lim
Parameters::Motor Control::Torque Limit
REAL
150.0
-300.0 to 300.0
%
ALWAYS
TECHNICIAN
01357
0416 Negative Torque Lim
Parameters::Motor Control::Torque Limit
REAL
-150.0
-300.0 to 300.0
%
ALWAYS
TECHNICIAN
01359
0417 Main Torque Lim
Setup::Motor Control::Control and Type
Parameters::Motor Control::Torque Limit
REAL
150.0
0.0 to 300.0
%
ALWAYS
TECHNICIAN
01361
0418 Fast Stop Torque Lim
Parameters::Motor Control::Torque Limit
REAL
150.0
0.0 to 300.0
%
ALWAYS
TECHNICIAN
01363
0419 Symmetric Torque Lim
Parameters::Motor Control::Torque Limit
BOOL
FALSE
ALWAYS
TECHNICIAN
01365
0420 Actual Pos Torque Lim
Monitor::Motor and Drive
Parameters::Motor Control::Torque Limit
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01367
0421 Actual Neg Torque Lim
Same as PNO 420
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01369
0422 VHz Shape
Setup::Motor Control::Control and Type
Parameters::Motor Control::Fluxing VHz
USINT
(enum)
0
0:LINEAR LAW
1:FAN LAW
2:USER DEFINED
3:APPLICATION DEFINED
STOPPED
TECHNICIAN
01371
0423 VHz User Freq
Parameters::Motor Control::Fluxing VHz
ARRAY[0..10]
STOPPED
ENGINEER
01373
0424 VHz User Freq[0]
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 100.0
%
STOPPED
ENGINEER
01375
0425 VHz User Freq[1]
Parameters::Motor Control::Fluxing VHz
REAL
10.0
0.0 to 100.0
%
STOPPED
ENGINEER
01377
0426 VHz User Freq[2]
Parameters::Motor Control::Fluxing VHz
REAL
20.0
0.0 to 100.0
%
STOPPED
ENGINEER
01379
0427 VHz User Freq[3]
Parameters::Motor Control::Fluxing VHz
REAL
30.0
0.0 to 100.0
%
STOPPED
ENGINEER
01381
0428 VHz User Freq[4]
Parameters::Motor Control::Fluxing VHz
REAL
40.0
0.0 to 100.0
%
STOPPED
ENGINEER
01383
0429 VHz User Freq[5]
Parameters::Motor Control::Fluxing VHz
REAL
50.0
0.0 to 100.0
%
STOPPED
ENGINEER
01385
0430 VHz User Freq[6]
Parameters::Motor Control::Fluxing VHz
REAL
60.0
0.0 to 100.0
%
STOPPED
ENGINEER
01387
0431 VHz User Freq[7]
Parameters::Motor Control::Fluxing VHz
REAL
70.0
0.0 to 100.0
%
STOPPED
ENGINEER
01389
0432 VHz User Freq[8]
Parameters::Motor Control::Fluxing VHz
REAL
80.0
0.0 to 100.0
%
STOPPED
ENGINEER
01391
0433 VHz User Freq[9]
Parameters::Motor Control::Fluxing VHz
REAL
90.0
0.0 to 100.0
%
STOPPED
ENGINEER
01393
0434 VHz User Freq[10]
Parameters::Motor Control::Fluxing VHz
REAL
100.0
0.0 to 100.0
%
STOPPED
ENGINEER
01395